Menu
Parameter
Description
Supply air
temp to
forcibly start
cooling
When the supply air temperature exceeds
the value of this parameter, the cooling
component is forcibly started.
Return air
temp to
forcibly start
cooling
When the return air temperature exceeds
the value of this parameter, the cooling
component is forcibly started.
Cold aisle
temp to
forcibly start
cooling
When the temperature of the cold aisle
exceeds the value of this parameter, the
cooling component is forcibly started.
DO_1 action
Set this parameter to On or Off based on
the actual scenario.
DO_2 action
Set this parameter to On or Off based on
the actual scenario.
DO_1
Set this parameter to Smoke & Water
only, Critical alarm, Major alarm,
Alarm, or Startup status based on the
actual situation.
DO_2
Set this parameter to Smoke & Water
only, Critical alarm, Major alarm,
Alarm, or Startup status based on the
actual situation.
Floor water
overflow
alarm action
Shutdown, Inactivity, Only indoor fan
running, or Humidification stopped can
be set as required.
In-cabinet
water
overflow
alarm action
Set this parameter to Shutdown,
Inactivity, Only indoor fan running,
Humidifier stopped, or Comm & Humid
stopped based on site requirements.
Dual power
supply
setting
Primary power first or Primary power
only can be set as required.
Power limit
function
This parameter can be set to Enable or
Disable.
System
power limit
This parameter ensures that the total
operating power of the system is always
below the preset value.
Cooling
mode
control
Select a running mode.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
C Parameter Description
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
266