Parameter
Description
High
humidity
alarm
When detecting that the alarm value is
greater than the threshold, the system
generates an alarm.
Low
humidity
alarm
When detecting that the alarm value is
greater than the threshold, the system
generates an alarm.
Settings > Alarm
Settings >
Mainboard
Return air
filter
blocked
alarm
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
Primary
power
failure alarm
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
SPD and
voltage
detection
board comm
failed
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
Backup
power
failure alarm
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
Outdoor
intake air
filter
blocked
alarm
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
Power
voltage
abnormal
Specifies the threshold.
NOTE
Use the default value.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
C Parameter Description