Item
Specifications
(Building Scenario)
Specifications (FDC Scenario)
1
Test conditions: The outdoor dry and wet bulb temperatures are 35°C and 27°C
respectively; the indoor return and supply air temperatures are 38°C at 25% RH
and 25°C at 50% RH respectively; the external residual pressures of the indoor
and outdoor units are 150 Pa and 100 Pa respectively. If the indoor return air
temperature is lower than 38°C, the cooling capacity of the equipment is
derated.
Table 2-6 Compressor cooling specifications
Item
Specifications
Compressor type
Variable-frequency scroll compressor
Number of compressors
3
Throttling device
Electronic expansion valve (EEV)
Refrigerant
R410A
2.7 Working Modes
The unit runs in one of the following modes based on the real-time working
conditions and load.
Table 2-7 Cooling modes
Cooling Mode
Fan
Status
Water
Pump
Status
Compressor
Status
Dry mode (fan)
On
Off
Off
Wet mode (fan + spraying)
On
On
Off
Dry mode + Auxiliary cooling
mode (fan + compressor
cooling)
On
Off
On
Wet mode + Auxiliary cooling
mode (fan + sp
compressor cooling)
On
On
On
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual