Figure 8-12 Removing a T/H sensor
Step 5 Disconnect the cable from the T/H sensor.
Step 6 Slide and remove the T/H sensor.
Step 7 Install the new T/H sensor and reconnect the cable.
NO TICE
Before installing the new T/H sensor, check that its DIP switch settings are
consistent with the DIP switch settings of the old T/H sensor.
Step 8 Power on the device and tap Start on the home screen. Ensure that the device is
running properly without generating alarms.
----End
8.5.8 Replacing a T/H Sensor (FDC Scenario)
Prerequisites
●
A T/H sensor needs to be replaced.
●
A spare T/H sensor of the same model is available and functional.
●
Tools: Phillips screwdriver, scissors
Procedure
Step 1 On the home screen of the display module, tap Shutdown and turn off the device
switch in the PDF.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual