Menu
Parameter
Description
Link mode
● Server: The smart cooling product
works as the server and can connect
to two clients for communication.
● Client: The smart cooling product
works as the client and can connect to
a remote server for communication.
● Server and client: The smart cooling
product works as the server and can
connect to two clients for
communication. It also works as the
client and can connect to a remote
server for communication.
Client
encryption
This parameter is configurable when Link
mode is set to Client.
Server
encryption
This parameter is configurable when Link
mode is set to Server.
Encryption
operation
CBC
Enable, Disable
NOTE
Indicates whether to use the CBC encryption
algorithm. When you set this parameter, a
dialog box is displayed, indicating that the
system will automatically restart. Select an
option based on the site requirements.
NMS IP
address
Enter the actual IP address of the NMS.
IP addresses of the display panel, client
NMS, and server NMS must be unique.
This parameter is configurable when Link
mode is set to Client.
NMS port
number
It is recommended that you retain the
default value. If you need to change the
value, enter a value as required. This
parameter is configurable when Link
mode is set to Client.
Pre-shared
password
Secondary authentication password used
for Modbus-TCP connection.
Settings > Comm
Settings > SNMP
Settings
For details, see the section "Setting Communications
Parameters."
Settings > Alarm
Settings > T/H
Sensor
Supply air*
temperature
sensor fault
● Enable: Alarms are reported to the
NMS. Active alarms are displayed on
the display module and the system
performs related protection actions.
● Disable: No alarms are generated and
no protection actions are performed.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
C Parameter Description
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.