Figure 8-28 Separating the suction and discharge welding joints
(1) Suction port
(2) Discharge port
NO TICE
After removing the compressor, block the suction inlet and exhaust outlet
immediately to ensure the system cleanness and prevent water from entering.
2. Use a 13# socket wrench (or solid wrench) to remove the four nut washers
and spring washers that secure the compressor and remove the compressor.
NO TICE
Do not hold the suction inlet and exhaust outlet to move the compressor.
Figure 8-29 Removing a compressor
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
8 System Maintenance
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
210