8.2.1 Monthly Maintenance
Table 8-1 Monthly maintenance checklist
Item
Expected Result
Troubleshooting
Air filter
The air filter is clean and not
blocked.
● The outdoor intake air filter
(level: G3) cannot be cleaned
with water. It is recommended
that the outdoor intake air filter
be replaced every six months.
● The return air filter cannot be
cleaned with water. It is
recommended that the return
air filter be replaced every six
months.
The air filter is not damaged
or distorted.
Replace the air filter.
Water
tank
The float has no scale.
Clean up the scale on the liquid
level sensor when the device is
shut down.
The water tank filter is not
blocked.
Clean up the foreign matter on the
surface of the water tank filter.
Compresso
r
The compressor is secured.
Tighten screws if the compressor is
not secured.
The operating compressor
generates no metal friction
noise or collision noise from
inside.
Replace the compressor.
Pipe
The refrigerant pipe does not
leak or corrode, and is
properly wrapped with
thermal insulation foam.
Repair the leakage points and
rewrap thermal insulation foam.
Wear working gloves and
touch the needle valve and
soldering points of the
refrigerant pipe. There are no
oil stains.
If there are oil stains, check
whether the suction and discharge
pressure of the compressor is
within the normal ranges. If the
pressure is beyond the normal
range, contact Huawei technical
support.
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
8 System Maintenance
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
136