Button
Button
Operation
Function
When the
smart cooling
product is
shut down,
hold down
the button for
more than
10s.
A dialog box is displayed, asking you whether
to restore the factory settings.
2.5 Operating Environment Specifications
Environmental Specifications
Table 2-2 Environmental specifications
Item
Specifications
Operating
temperature
–40°C to +45°C
Operating humidity
5%–95% RH
Storage temperature
–40°C to +70°C
Storage humidity
5%–95% RH
Altitude
The performance is not derated when the altitude is
below 1000 m, and is derated when the altitude ranges
from 1000 m to 4000 m.
Table 2-3 Derating coefficients
Altitude
(m)
[0,100
0)
1000 1500
200
0
2500
3000
3500
4000
Air volume
coefficient
1
0.887 0.835
0.78
5
0.737
0.692
0.649
0.608
Cooling
capacity
coefficient
1
0.887 0.835
0.78
5
0.737
0.692
0.649
0.608
Note: The sensible heat ratio is always 100%.