Step 5 Start the unit, set the indoor fan speed to the maximum value, and read the
pressures measured at the positive and negative pressure points.
NO TE
Choose Maint > Diagnostic Mode > Enter and set the indoor fan speed to the maximum
value.
Step 6 Tap Start on the home screen. Ensure that the device is running normally without
any alarms.
Step 7 Log in to the WebUI as user admin, choose Settings > System Settings > System
Control > Advanced, and set Static pressure.
Step 8 Choose Running > Status Summary and view the value of air volume.
NO TE
● Static pressure setting = Pressure measured at the positive pressure point – Pressure
measured at the negative pressure point.
● User operator can access customer and delivery parameters. The parameters on the
Advanced menu are delivery parameters. User admin can access customer, delivery,
maintenance, and R&D parameters. The parameters on the Advanced menu are R&D
parameters.
● To prevent the effect of misoperations on the system, log in as user operator before
modifying parameters. Confirm with Huawei technical support before modifying
parameters which cannot be modified by user operator. Otherwise, Huawei will not be
liable for any consequences of the modification performed by the user.
● Only certified professionals are allowed to modify advanced parameters of smart
cooling products. Unauthorized modifications can result in smart cooling product
malfunction and even damage.
Step 9 Remove the pressure tubes and seal the holes.
----End
9.1.13 How Do I Check Whether Group Upgrade Is Supported
in a Scenario?
During group upgrade, the unit that is being upgraded is shut down and then
restarted. Ensure that the cooling capacity of the remaining units meets the
cooling requirements to avoid insufficient cooling capacity.
Table 9-1 Networking scenarios for group upgrade
Networking
Scenario
Monitoring
System
Networking
Teamwork
Networking
Group Upgrade
Status
1
FE monitoring
FE teamwork
Supported
2
FE monitoring
CAN teamwork
Supported
3
RS485 monitoring FE teamwork
Supported
4
RS485 monitoring CAN teamwork
Not supported
FusionCol8000-E240 Modular Indirect Evaporative
Cooling System
User Manual
9 FAQ
Issue 02 (2021-04-15)
Copyright © Huawei Technologies Co., Ltd.
240