Figure 3-23 Safety Ground Reference Check
WARNING!
SHOCK HAZARD
Risk of shock hazard while testing primary power.
Use properly insulated probes.
Be sure to replace access cover when finished testing primary power.
1.
Measure the voltage between A0 and A1 as follows:
1.
Take the AC voltage down to the lowest scale on the volt meter.
2.
Insert the probe into the ground pin for A0.
3.
Insert the other probe into the ground pin for A1.
4.
Verify that the measurement is between 0-5 V AC.
If the measurement is 5 V or greater, escalate the situation. Do not attempt to plug the power
cord into the server cabinet.
2.
Measure the voltage between B0 and B1 as follows:
1.
Take the AC voltage down to the lowest scale on the volt meter.
2.
Insert the probe into the ground pin for B0.
3.
Insert the other probe into the ground pin for B1.
4.
Verify that the measurement is between 0-5 V AC.
If the measurement is 5 V or greater, escalate the situation. Do not attempt to plug the power
cord into the server cabinet.
3.
Measure the voltage between A0 and B0 as follows:
1.
Take the AC voltage down to the lowest scale on the volt meter.
2.
Insert the probe into the ground pin for A0.
3.
Insert the other probe into the ground pin for B0.
4.
Verify that the measurement is between 0-5 V AC.
If the measurement is 5 V or greater, escalate the situation. Do not attempt to plug the power
cord into the server cabinet.
70
Installing the Server
Summary of Contents for Integrity rx7640
Page 8: ...8 ...
Page 12: ...12 ...
Page 13: ...List of Examples 4 1 Single User HP UX Boot 101 7 1 Single User HP UX Boot 181 13 ...
Page 14: ...14 ...
Page 42: ...42 ...
Page 88: ...88 ...
Page 130: ...Figure 5 8 Core I O Button Locations OLR MP Reset 130 Server Troubleshooting ...
Page 140: ...140 ...
Page 176: ...176 ...
Page 184: ...184 ...
Page 191: ...Figure C 3 Planning Grid Computer Room Layout Plan 191 ...