CAUTION:
Use caution when handling the BPS. A BPS weighs 18 lbs.
Replacing a BPS
1.
Verify that the extraction levers are in the open position, then insert the BPS into the empty
slot.
2.
The BPS easily slides into the chassis. Use a slow firm pressure to properly seat the connection.
3.
Ensure the BPS has seated by closing the extraction levers.
4.
Replace the front bezel.
NOTE:
The BPS LED should show BPS operational and no fault. The BPS LED should be
GREEN.
Configuring Management Processor (MP) Network Settings
After removing and replacing the core I/O in the server, verify the MP LAN network settings,
using the settings from the original (replaced) core I/O.
To configure management processor network settings, use the MP Command menu’s
LC
command.
To list the current management processor (MP) network configuration, use the
LS
command.
Default Management Processor Network Settings
Table 6-6
lists an example of the default MP
LAN network settings for the server.
Table 6-6 Default Configuration for Management Processor LAN
192.168.1.1
MP LAN IP Address
gsp0
MP LAN Host Name
255.255.255.0
MP LAN Subnet Mask
192.168.1.1
MP LAN Gateway
This procedure (Command menu,
LC
command) configures the management processor’s MP
LAN network settings from the management processor Command menu.
174
Removing and Replacing Components
Summary of Contents for Integrity rx7640
Page 8: ...8 ...
Page 12: ...12 ...
Page 13: ...List of Examples 4 1 Single User HP UX Boot 101 7 1 Single User HP UX Boot 181 13 ...
Page 14: ...14 ...
Page 42: ...42 ...
Page 88: ...88 ...
Page 130: ...Figure 5 8 Core I O Button Locations OLR MP Reset 130 Server Troubleshooting ...
Page 140: ...140 ...
Page 176: ...176 ...
Page 184: ...184 ...
Page 191: ...Figure C 3 Planning Grid Computer Room Layout Plan 191 ...