C05.10 Terminal RUN Digital Input
Default setting
8
C05.11 Terminal F/R Digital Input
Default setting
10
C05.12 Terminal RST Digital Input
Default setting
1
C05.13 Terminal JOG Digital Input
Default setting
14
C05.15 Terminal EMS Digital Input
Default setting
16
Range
See the following table
[0] No Operation
The frequency converter will not
react to signals transmitted to the
terminal.
[1] Reset
Reset the frequency converter after
a Trip/Alarm. Not all alarms can be
reset.
[2 ] Coast Inverse
Coasting stop, inverted input (NC).
The frequency converter leaves the
motor in free mode.
[3] Coast and reset inv.
Reset and coasting stop inverted input
(NC). The frequency converter resets
and leaves the motor in free mode.
[4] Quick stop inverse
Inverted input (NC). Generates a stop
in accordance with the quick-stop
ramp time set in par. C03.81. When
motor stops, shaft is in free mode.
[5] DC-brake inv.
Inverted input for DC braking (NC).
Stops motor by energizing it with DC
current for a certain time period, see
par. C02.01. Function is only active
when value in par. C02.02 is different
from 0.
[6] Stop inv.
Stop inverted function. Generates
stop function when selected terminal
goes from logical level “1” to “0”.
Stop is perfor med according to
selected ramp time.
[8] Start
Select start for a start/stop command.
1 = Start, 0 = stop.
[9] Latched start
Motor starts if a pulse is applied for
min. 2 ms. Motor stops when Stop
inverse is activated.
[10] Reversing
Change direction of motor shaft
rotation. Reversing sig nal only