HLP-NV Series
HLP-NV Series
-
73
-
C07.30 Process PI Normal/ Inverse Ctrl Default setting
0
Range
[0] Normal Feedback larger than setpoint result
in a speed reduction.
Feedback less than setpoint result
in a speed increase.
[1] Inverse Feedback larger than setpoint result
in a speed increase.
Feedback less than setpoint result
in a speed reduction.
C07.20 Process CL Feedback 1 Resource Default setting
0
Range
[0]
No Function
[1] Analog Input VIN
[2] Analog Input AIN
[8] Pulse Input 33
[11] Local Bus Ref.
Parameter group 7: Controllers
Parameters group for configuring application controls.
C07.2* Process Ctrl. Feedb
Select feedback sources and handling for Process PI Control.
●
Function:
Select input to function as feedback signal.
C07.3* Process PI Control