HLP-NV Series
HLP-NV Series
-
70
-
●
Function:
A first-order digital low pass filter time constant for
suppressing electrical noise in Terminal VIN. A high time constant
value improves dampening but also increases time delay through the
filter.
●
ATTENTION!
This parameter cannot be adjust while motor is
running.
C06.16 Terminal VIN Filter Time Constant Default setting 0.01s
Range
[0.01 - 10.00 s] Enter time constant.
C06.19 Terminal VIN mode
Default setting
0
Range
[0] [0] * Voltage Mode
[1] [1] Current Mode
●
Function:
Select the input to be present on Terminal VIN.
●
Warning:
Par. C06.19 MUST be set according to Micro switch XXX
setting.
C06.2* Analog Input 2
Parameters for configuring scaling and limits for analog input 2,
Terminal AIN.
●
Function:
This reference signal should correspond to minimum
reference value set in par. C03.02.
●
Warining:
The value must be set to min. 2 mA in order to activate the
Live Zero Timeout function in par. C06.01.
C06.22 Terminal AIN Low Current Default setting 0.14
Range
[0.00 - 19.99 mA] Enter low current value.
●
Function:
This reference signal should correspond to the high current
value set in par. C06.25.
C06.23 Terminal AIN High Current Default setting 20.00
Range
[0.10 - 20.00 mA] Enter high current value.
●
Function:
The scaling value should correspond to the minimum
reference feedback value set in par. C03.02.
C06.24 Term. AIN Low Ref./Feedb. Value Default setting 0.000
Range [-4999.000 -4999.000]
Enter analog input scaling value.
●
Function:
The scaling value should correspond to the maximum
reference feedback value set in par. C03.03.
C06.25 Term. AIN High Ref./Feedb. Value Default setting 50.000
Range
[-4999.000 -4999.000]
Enter analog input scaling value.