HLP-NV Series
HLP-NV Series
-
54
-
the Catch-up/Slowdown value (in %) is added to the reference function
as follows:
Reference = Ref reference × Catchup Slowdown /100
Reference = Reference - reference × Catchup Slowdown /100
When the input command is inactivated, the reference returns to its
original value ie. Reference = Ref 0.
C03.14 Preset Relative Reference
Default setting 0.00%
Range
[-100.00 - 100.00%]
●
Function:
Define fixed value in % to be added to variable value
defined in par. C03.18, Relative Scaling Reference Source. The sum of
fixed and variable values (labelled Y in illustration below) is multiplied
with actual reference (labelled X in illustation). This product is added
to actual reference X + X *Y /100
C03.15 Reference Resource 1
Default setting
1
Range
[0] No Function No reference signal is defined.
[1] Analog Input VIN
Use signals from analog Input VIN
as reference, see par. C06.1*.
[2] Analog Input AIN
Use signals from analog Input AIN
as reference, see par. C06.2*.
[8] Pulse input Use signals from pulse input as
reference, see par. C05.5*.
[11] Local Bus Ref.
Use signals from local bus as
reference, see par. C08.9*.
[21] LCP Potentiometer
U s e s i g n a l s f r o m L C P
potentiometer as reference, see par.
C06.8*.
●
Function:
Par. C03.15, C03.16 and C03.17 define up to three different
reference signals. The sum of these reference signals defines the actual
reference.