Function:
Set the Maximum Motor Speed corresponding to the
maximum output frequency of the motor shaft.
●
ATTENTION!
As the maximum output frequency is an absolute
value, it cannot be deviated from.
C04.14 Motor Speed High Limit [Hz] Default setting 65.0HZ
Range
[0.0 - 400.0 Hz]
●
Function:
Set the torque limit for motor operation.
The setting is not automatically reset to default when changing settings
in par. C01.00 to C01.25 Load & Motor .
C04.16 Torque Limit Motor Mode
Default setting 150%
Range
[0 - 400%]
●
Function:
Set the torque limit for generator mode operation.
The setting is not automatically reset to default when changing settings
in par. C01.00 to C01.25 Load & Motor.
C04.17 Torque Limit Generator Mode Default setting 100%
Range
[0 - 400 %]
C04.5* Adjustable Warnings
Parameter group containing adjustable warning limits for current, speed,
reference and feedback.
Warnings are shown in display, programmed output or serial bus.
●
Function:
Use this parameter to set a lower limit for the current
range. If current drops below the set limit, a warning occurs.
C04.50 Warning Current Low
Default setting 0.00A
Range
[0.00 - 26.00 A]
●
Function:
Use this parameter to set an upper limit for the current
range. If current exceeds the set limit, a warning occurs.
C04.51 Warning Current High
Default setting26.00A
Range
[0.00 - 100.00 A]
C04.58 Missing Motor Phase Function Default setting
1
Range
[0] Off Function is disabled.
[1] On Function is enabled.