1-7* Start Adjustments
Considering the need for various start functions in different applications,
it is possible to select a number of functions in this parameter group.
C01.71 Start Delay
Default setting 0.0S
Range
[0.0 - 10.0 s]
●
Function:
The start delay defines the time to pass from a start
command is given until the motor starts accelerating.
Setting start delay to 0.0 sec. disables Start Function, [C01.72], when
start command is given.
Enter the time delay required before commencing acceleration. Par.
C01.72 Start Function is active during Start delay time .
C01.72 Start Function
Default setting
2
Range
[0] DC Hold/Delay Time Motor is energized with
DC holding current (par.
C02.00) du r ing star t
delay time.
[1] DC Brake/Delay Time Motor is energized with
DC braking current (par.
C02.01) du r i ng st a r t
delay time.
[2] Coast/Delay Time
I n v e r t e r i s c o a s t e d
during start delay time
(inverter off).
C01.73 Flying Start
Default setting
0
Range
[0] Disabled Flying start is not required.
[1] Enabled Frequency converter enabled to
catch spinning motor.
●
Function:
Use flying start to catch a spinning motor after eg. mains
dropout.
●
Warning:
This function is not suitable for hoisting applications.
●
ATTENTION!
When flying start is enabled par. C01.71, Start Delay,
and par. C01.72, Start Function, have no function.