HLP-NV Series
HLP-NV Series
-
53
-
3-1* References
Parameters for setting up the reference sources. Select the preset
references for the corresponding digital inputs in parameter group 5.1*,
Digital Inputs.
18 Bit2
17 Bit1
16 Bit0
Preset reference no.
0
0
0
0
0
0
1
1
0
1
0
2
0
1
1
3
1
0
0
4
1
0
1
5
1
1
0
6
1
1
1
7
Table 4.1: Par. C05.1* selection [16], [17] and [18]
C03.10 Preset Reference
Default setting 0.00%
Range
[ -100.00 - 100.00%]
●
Function:
Each parameter set-up contains 8 preset references which
are selectable via 3 digital inputs or bus.
Enter the different preset references using array programming.
Normally, 100% = value set in par. C03.03,
Maximum Reference. However, there are exceptions if par. C03.00 is
set to Min - Max, [0].
Example 1: Par. C03.02 is set to 20 and par. C03.03 is set to 50. In this
case 0%= 0 and 100% = 50.
Example 2: Par. C03.02 is set to -70 and par. C03.03 is set to 50. In this
case 0% = 0 and 100% = 70.
C03.11 Jog Speed [Hz]
Default setting 5.0HZ
Range
[0.0 - 400.0 Hz] Select speed to function as jog speed.
●
Function:
Jog speed is a fixed output speed and overrules the selected
reference speed, see par. C05.1* selection [14].
If the motor is stopped while in jog mode, the jog signal acts as a start
signal. Removing the jog signal makes the motor run according to the
selected configuration.
C03.12 Catch up/slow Down Value
Default setting 0.00%
Range
[0.00 – 100.00%]
●
Function:
The Catch-up/Slowdown function is activated by an input
command (see par. C05.1*, choice [28]/[29]). If the command is active,