C01.00 Configuration Mode
Default setting
0
Range
[0] Speed open loop For normal speed control
(References).
[3] Process Closed Loop Enables process closed
l o o p c o n t r ol . S e e p a r.
group C07.3* or further
i n f o r m a t i o n o n P I -
controller.
When running in process
closed loop, par. C04.10
Motor Speed Direction must
be set to Clockwise [0]
C00.40 [Hand on] Key o
n LCP
Default setting
1
Range
[0] Disabled Hand-on key has no function.
[1] Enabled Hand-on key is functional.
C00.41 [Off / Reset] Key on LCP
Default setting
1
Range
[0] Disable Off/Reset Off/reset key has no
function.
[1] Enable Off/Reset Stop signal and reset of
any faults.
[2] Enable Reset Only Reset only. Stop (Off)
function is disabled.
C00.42 [Auto on] Key on LCP
Default setting
1
Range
[0] Disabled Auto-on key has no function.
[1] Enabled Auto-on key is functional.
Parameter group 1: Load/Motor
●
Function:
Use this parameter for selecting the application control
principle to be used when a Remote Reference is active.
C00.60 Menu Locked
Default setting
0
Range
[0] Disable allow for changing parameter
values
[1] Enable parameter can be read,but can’t be
edited