HLP-NV Series
HLP-NV Series
-
43
-
C01.33 Stator Leakage Reactance (X1) Default setting
**
Range
Depending on motor data*[Ohm]
●
Function
:
Set stator leakage reactance of motor.
C01.35 Main Reactance (Xh)
Default setting
**
Range
Depending on motor data*[Ohm]
●
Function
:
Set motor main reactance.
1-5* Load Independent Setting
This parameter group is for setting the load independent motor settings.
C01.50 Motor Magnetisation at 0 Speed Default setting 100%
Range
[ 0 - 300%] Enter a percentage of rated magnetizing
current. If setting is too low, motor shaft
torque may be reduced.
●
Function
:
This parameter enables different thermal load on motor
when running at low speed.
C01.52 Min Speed Norm. Magnet. [Hz] Default setting 0.0HZ
Range
[0.0 - 10.0 Hz]
●
Function
:
Use this parameter along with par. C01.50, Motor
Magnetizing at Zero Speed.
Set frequency required for normal magnetizing current. If frequency is
set lower than motor slip frequency, par. C01.50, Motor Magnetizing at
Zero Speed is inactive.
C01.55 V/F Characteristic - U
Default setting 0V
Range
[0 - 999 V]
●
Function:
This parameter is an array parameter [0-5] and is only
functional when par. C01.01, Motor Control Principle is set to V/F [0].
Enter voltage at each frequency point to manually form a V/F
characteristic matching motor. Frequency points are defined in par.
C01.56, V/F characteristics - F.