HLP-NV Series
HLP-NV Series
-
81
-
C14.20 Reset Mode
Default setting
0
Range
[0] Manu
al Reset Perform reset via [reset]-button or digital
inputs.
[1] AutoReset 1 Performs one automatic reset after
tripping.
[2] AutoReset 2 Performs two automatic resets after
tripping.
[3] AutoReset 3 Performs three automatic resets after
tripping.
[4] AutoReset 4 Performs four automatic resets after
tripping.
[5] AutoReset 5 Performs five automatic resets after
tripping.
[6] AutoReset 6 Performs six automatic resets after
tripping.
[7] AutoReset 7 Performs seven automatic resets after
tripping.
[8] AutoReset 8 Performs eight automatic resets after
tripping.
[9] AutoReset 9 Performs nine automatic resets after
tripping.
[10] AutoReset 10 Performs ten automatic resets after
tripping.
[11] AutoReset 15 Performs fifteen automatic resets after
tripping.
[12] AutoReset 20 Performs twenty automatic resets after
tripping.
[13] Infinite auto reset Performs an infinite number of
automatic resets after tripping.
●
Function:
This feature allows more accurate speed control near
and over nominal speed (50/60 Hz). Another advantage with
overmodulation is the ability of staying at a constant speed even
though mains is dropping.
14-1* Mains Monitoring
This parameter group supplies functions for handling imbalance on mains.
C14.12 Function at mains imbalance Default setting
0
Range
[0] Trip Frequency converter trips
[1] Warning Frequency converter issues a warning.
[2] Disabled No action taken.
●
Function:
Operation under severe mains imbalance conditions
reduces drive lift time.
Select function to take place when severe mains imbalance is detected.
14-2* Trip Reset
Parameters for configuring auto reset handling, special trip handling and
control card self test or initialisation.