HLP-NV Series
HLP-NV Series
-
25
-
VII. Parameter Overview
Item
Function
Code Fuction Description
Range&Function
explanation
Default
setting
Operation
/ Display
C00.04
Oper. State at Power-
up [Hand]
[0] Resume
*[1] Forced stop, ref =
old
[2] Forced stop, ref = 0
1
C00.31
Custom Readout Min
Scale
0.00 – 9999.00
0.00
C00.32
Custom Readout Max
Scale
0.00 – 9999.00
100.00
C00.40
[Hand on] Key on LCP
[0] Disabled
*[1] Enabled
1
C00.41 [Off / Reset] Key on
LCP
[0] Disable All
*[1] Enable All
[2] Enable Reset Only
1
C00.42
[Auto on] Key on LCP
[0] Disabled
*[1] Enabled
1
C00.60
Menu locked
[0]Disabled
[1]Enabled
0
Load /
Motor
C01.00 Configuration Mode
*[0] Speed open loop
[3] Process
0
C01.01
Motor Control
Principle
[0] V/F
*[1] VVC+
1
C01.03 Torque Characteristics
*[0] Constant torque
[2] Automatic Energy
Optim.
0
C01.05
Local Mode
Configuration
[0] Speed Open Loop
*[2] As config in param.
C01.00
2
C01.20
Motor Power
[kW] [HP]
0.09 kW / 0.12 HP .... 11
kW / 15 HP
**
C01.22
Motor Voltage
50 - 999 V
**
C01.23 Motor Frequency
20 - 400 Hz
50 Hz
C01.24
Motor Current
0.01 - 26.00 A
**
C01.25
Motor Nominal Speed
100 - 9999 rpm
**
C01.29
Automatic Motor
Tuning (AMT)
*[0] Off
[2] Enable AMT
0
C01.30
Stator Resistance (Rs) [Ohm] * Dep. on motor
data
**