C06.91 Terminal AON Analog Output Default setting
10
Range
[0]
No Operation
[10] Output Frequency
[11] Reference
[12] Feedback
[13] Motor Current
[16] Power
[20] Speed
●
Function:
Select the function for Terminal AON as an analog output.
●
Function:
See par. C05.4*,Relays, for choices and descriptions.
C06.92 Terminal AON Digital Output Default setting
0
Range
See par. C05.4*,
●
Function:
Scale minimum output of selected analog signal at Terminal
AON as percentage of maximum signal value. E.g. if 0 mA (or 0 Hz)
is desired at 25% of maximum output value, programme 25%. Scaling
values up to 100% can never be higher than corresponding setting in
par. C06.52.
C06.93 Terminal AON Output Min Scale Default setting 0.00%
Range
[0.00 - 200.00%]
●
Function:
Scale maximum output of selected analog signal at
Terminal AON. Set value to maximum value of current signal output.
Scale output to give a current lower than 20 mA at full scale; or 20
mA at an output below 100% of maximum signal value. If 20 mA
is the desired output current at a value between 0 -100% of the full-
scale output, programme percentage value in the parameter, i.e. 50%
= 20 mA. If a current between 4 and 20 mA is desired at maximum
output (100%), calculate percentage value as follows: 20 mA/desired
maximum current × 100 %
i.e. 10 mA = 20/10 × 100 = 200%
C06.94 Terminal AON Output Max Scale Default setting 100.00%
Range
[0.00 – 200.00%]