HLP-NV Series
HLP-NV Series
-
80
-
C08.56 Preset Reference Select
Default setting
3
Range
[0] Digital Input
Activation via a digital input.
[1] Bus Activation via serial
communication port.
[2] LogicAnd Activation via serial
communication port and a digital
input.
[3] LogicOr Activation via serial
communication port or a digital
input.
●
Function:
Select control of Preset Reference selection via digital input and/
or bus.
8-9* Bus Feedback
Parameter for configuring bus feedback.
C08.94 Bus feedback 1
Default setting
0
Range
0* [0x8000 - 0x7FFF]
Parameter group 14: Special Functions
Parameter group for configuring special frequency converter functions.
14-0* Inverter Switching
Parameters for configuring the inverter switching.
C14.01 Switching Frequency
Default setting
1
Range
[0] 2 KHZ
[1] 4KHZ
[2] 8KHZ
[4] 16KHZ
●
Function:
Select the switching frequency in order to minimize e.g.
acoustic noise and power loss or maximizing efficiency.
C14.03 Overmodulation
Default setting
1
Range
[0] Off
Disable s t he ove r modu lat ion
function to avoid torque ripple on
the motor shaft.
[1] On
Con nects the over modulation
function to obtain an output voltage
up to 15% greater than mains
voltage.