HLP-NV Series
HLP-NV Series
-
48
-
C01.93 Thermistor Resource
Default setting
0
Range
[0] None
No thermistor is connected.
[1] Analog Input VIN
Connect thermistor to analog input
Terminal VIN.
[6] Digital Input JOG
Connect thermistor to digital input
Terminal JOG.
W hile this input f unctions as
t he r m i s t o r i n put , it w i l l not
respond to the function chosen in
par. C05.13, Digital Input JOG.
The value of par. C05.13 remains
however unchanged in parameter
database while function is inactive.
C01.90 Motor Thermal Protection
Default setting
3
Range
[0] No Protection
Disables temperature monitoring.
[1] Thermistor Warning
A thermistor connected to either
digital or analog input gives a
warning if upper limit of motor
temperature range is exceeded, (see
par. C01.93, Thermistor Resource).
[2] Thermistor Trip
A thermistor connected to either
digital or analog input gives
an alarm and makes the frequency
converter trip if upper
limit of motor temperature range
is exceeded, (see par. C01.93,
Thermistor Resource.
[3] ETR Warning
If
calculated upper limit of motor
temperature range is exceeded, a
warning occurs.
[4] ETR Trip
If calculated upper limit of motor
temperature range is exceeded,
an alarm occurs and frequency
converter trips.
●
Function:
Using ETR (Electronic Terminal Relay) the motor
temperature is calculated based on frequency, speed and time. Danfoss
recommends using The ETR function, if a thermistor is not present.
●
ATTENTION!
ETR calculation is based on motor data from group
C01.2*.