HLP-NV Series
HLP-NV Series
-
47
-
C01.80 Function at Stop
Default setting
0
Range
[0] Coast
The inverter is coasted.
[1] DC hold The motor is energized with a DC
current. See par. C02.00 DC Hold
Current for more information.
C01.8* Stop Adjustments
To meet the need for various stop functions in different application these
parameters offer some special stop features for the motor.
●
Function:
The selected function at stop is active in following
situations:
■ Stop command is given and output speed is ramped down to Min.
Speed for Activating Functions at Stop.
■ Start command is removed (standby), and output speed is ramped
down to Min. Speed for Activating Functions at Stop.
■ DC-brake command is given, and DC-brake time has passed
■ While running and calculated output speed is below Min. Speed for
Activating Functions at Stop.
C01.82 Min Speed for Funct. at Stop [Hz] Default setting 0.0HZ
Range
[0.0 - 20.0 Hz]
●
Function:
Set the speed at which to activate par. C01.80 Function at
Stop.
C01.9* Motor Temperature
With an estimated motor temperature monitor the frequency converter is
able to estimate motor temperature without having a thermistor mounted.
It is thus possible to receive a warning or an alarm, if motor temperature
exceeds upper operational limit.