HLP-NV Series
HLP-NV Series
-
67
-
●
Function:
Set reference/feedback value corresponding to low pulse
frequency value set in par. C05.55.
C05.57 Term. EMS Low Ref./Feedb. Value Default setting 0.000
Range
[-4999.000 -4999.000]
●
Function:
Set reference/feedback value corresponding to high pulse
frequency value set in par. C05.56.
C05.58 Term. EMS High Ref./Feedb. Value Default setting 50.000
Range
[-4999.000 -4999.000]
Parameter group 6: Analog In/Out
Parameter group for configuring analog inputs and outputs.
C06.0* Analog I/O Mode
Parameter group for setting up the analog I/O configuration.
●
Function:
The Live Zero function is used for monitoring the signal
on an analog input. If the signal disappears, a Live Zero warning is
reported.
Set delay time before Live Zero Timeout Function is applied (par.
C06.01).
If the signal reappears during the set delay, timer will be reset. When
live zero is detected, the frequency converter freezes output frequency
and starts Live Zero Timeout timer.
C06.00 Live Zero Timeout Time
Default setting 10s
Range
[1 - 99 s]