C08.04 Control Word Timeout Function Default setting
0
Range
[0] Off No function.
[1] Freeze Output
Freeze output until communication
resumes.
[2] Stop
St o p w it h a u t o r e s t a r t wh e n
communication resumes.
[3] Jogging
Run motor at jog frequency until
communication resumes.
[4] Max. Speed
Run motor at max. frequency until
communication resumes.
[5] Stop and Trip
Stop motor, then reset frequency
converter in order to restart either
via LCP or digital input.
●
Function:
Select the action to be taken in case of a timeout.
C08.06 Reset Control Word Timeout Default setting
0
Range
[0] No Function Control word timeout is not reset.
[1] Do Reset Control word timeout is reset, and
parameter goes into No Function
state.
●
Function:
Resetting the control word timeout will remove any
timeout function.
8-3* FC Port Settings
Parameters for configuring the FC Port.
C08.30 Protocol
Default setting
0
Range
[0] FC
[1] MODBUS
●
Function:
Select the protocol to be used. Note that changing protocol
will not be effective until after powering off the frequency converter.