HLP-NV Series
HLP-NV Series
-
101
-
7: Process close loop control
(
PI control
)
Speed select table
(
0
:
OFF 1
:
ON
)
Speed
EMS
JOG
RST
Speed 1
0
0
0
Speed 2
0
0
1
Speed 3
0
1
0
Speed 4
0
1
1
Speed 5
1
0
0
Speed 6
1
0
1
Speed 7
1
1
0
Speed 8
1
1
1
C01.00 = 3
setpoint:
C03.15, C03.16, C03.17, C03.14, C03.18 defines the setpoint of PI
control
feedback:
C07.20 defines the feedback signal of PI control
Example: Use preset reference C03.10(0)as setpoint,
Use 4-20mA Analogue input as feedback
Parameters setting
C03.02 = 0 C03.03 = 50 C03.10(0)= 50%
C03.15 = C03.16 = C03.17 = C03.14 = C03.18 = 0
C06.12 = 4mA C06.13=20mA C06.14=0 C06.15=50 C06.19 = 1
C07.20 = 1(VI) C07.30= 0 C07.31 = 0 C07.32 = 0
C07.33 = 1.00 C07.34 = 10.00s C07.38 = 0 C07.39 = 50%
Trun on switch 4
Press "
Auto
" to active Auto mode
Connect RUN with EV to operate the drive.