HLP-NV Series
HLP-NV Series
-
77
-
●
Function:
Select the address for the bus.
FC -bus range is 1-126.
Modbus range is 1-247.
C08.31 Address
Default setting
1
Range
[1 - 126]
C08.32 FC Port Baud Rate
Default setting
2
Range
[0] 2400 Baud
[1] 4800 Baud
[2] 9600 Baud
[3] 19200 Baud
[4] 38400 Baud
●
Function:
Select baud rate for FC Port.
●
ATTENTION!
Changing baud rate will be effective after responding
to any ongoing bus-requests.
C08.33 FC Port Parity
Default setting
0
Range
[0] Even Parity(1 stopbit)
[1] Odd parity
[2]
No Parity (1 stopbit) Select this for Modbus RTU
[3] No Parity (2 stopbit)
●
Function:
This parameter only affects Modbus as FC bus always has
even parity.
●
Function:
Specify minimum delay time between receiving a request
and transmitting a response.
C08.35 Minimum Response Delay
Default setting 0.010s
Range
[0.001 -0. 500 s]
●
Function:
Specify maximum permissible delay time between
transmitting a request and receiving a response. Exceeding this time
delay causes control word timeout.
C08.36 Max Response Delay
Default setting 5.000s
Range
[0.010 - 10.000 s]