39
Function
code
Name
Setting range
Factory
value
Communica
tion address
F9-14
Fault protection action
option 1
Bits: motor overload ( OL2 )
0: free parking
1: shut down according to shutdown method
2. continue running
10 bits: input phase missing ( IPL )
100 bits: output phase missing (OPL)
1000 bits: external fault ( ETF )
10,000 bits: communication abnormality (COF)
00000
F90EH
F9-15
Fault protection action
option 2
Bits:
0: free parking
10 bits: abnormal reading and writing of function
code (E2F)
0: free parking
1: shut down according to shutdown method
100 bits: reserved
10,000 bits: running time arrival (rtAF)
00000
F90FH
F9-16
Fault protection action
option 3
Bits: user-defined fault 1 ( UEF1 )
0: free parking
1: shut down according to shutdown method
2: continue running
10 bits: user-defined fault 2 ( UEF2 )
0: free parking
1: shut down according to shutdown method
2: continue to run
100 bits: power on time (UTF)
0: free parking
1: shut down according to the shutdown party
2: continue to run
1000 bits: OFF load(LIF)
0: free parking
1: slow down and stop
2: Jump to 7 % of the rated frequency of the
motor to continue running directly, and
automatically return when the load is not OFF
loaded
10,000 bits: when running PID feedback loss
(PIDF)
0: free parking
1: shut down according to shutdown method
2: continue running
00000
F910H
F9-17
Fault protection action
option 4
Bits: excessive speed deviation ( DEU )
0: free parking
1: shut down according to shutdown method
2: continue to run for
10 bits: motor over speed ( OSF )
100 bits: initial position error ( poF )
00000
F911H
F9-21
Continue operating
frequency selection in
case of failure
0: run at current operating frequency
1: run at the set frequency
2: run at the upper limit frequency
3: the following limited frequency operation
4: run at abnormal standby frequency
0
F915H
F9-22
Abnormal standby
frequency
0.0 %
~
100.0 % ( 100.0 % corresponding to the
maximum frequency F0 - 16 )
100.0%
F916H
F9-23
Motor sensor type
0: none
1: PT100
2: PT1000
0
F917H
F9-24
Motor overheating
threshold
0°C
~
200°C
110
F918H
F9-25
Motor overheating
warning threshold
0°C
~
200°C
90
F919H