29
Function
code
Name
Setting range
Factory
value
Communica
tion address
F4 group output terminals
F4-00
FM terminal output mode
selection
0: pulse output
1. switch output
0
F400H
F4-01
FM switch output power
selection
0: no output
1: the frequency inverter is running
2: fault output ( fault for free shutdown )
3: frequency level detection FD t1 output
4: frequency arrival
5: zero speed operation ( no output during
shutdown )
6: motor overload pre - alarm
7: frequency inverter overload pre - alarm
8: set the count value to reach
9: specified count value arrives
10: length arrives
11: PLC cycle completed
12: accumulated operating time arrives
13: frequency limit
14: torque limit
15: operational readiness
16: AI1>AI2
17: upper limit frequency reached
18: lower limit frequency reached ( operation
related )
19: under voltage state output
20: communication settings
21: positioning completed ( reserved )
22: positioning approach ( reserved )
23: zero speed operation in 2 ( output when
shutdown )
24: cumulative power-on time arrives
25: frequency level detection FD T2 output
26: frequency 1 reaches output
27: frequency 2 reaches output
28: current 1 reaches output
29: current 2 reaches output
30: arrive at output regularly
31: AI1 input overrun
32: falling load
33: reverse operation
34: zero current state
35: module temperature reached
36: output current exceeds limit
37: lower limit frequency reached ( shutdown
also output )
38: alarm output ( all faults )
39: motor over temperature pre - alarm
40: the running time has arrived
41: fault output ( fault for free shutdown
And under-voltage does not output )
42: AI1 is lower than lower limit output, lower
limit F4 - 37
43: AI1 above upper limit output, upper limit F4 -
38
44: AI2 is lower than lower limit output, lower
limit F4 - 37
45: AI2 above upper limit output, upper limit F4 -
38
0
F401H
F4-02
Function selection of
control panel relay 1
(T/A-T/B-T/C)
2
F402H
F4-03
Function selection of
control panel relay 2
(T/A-T/B-T/C)
F4-04
DO1 output function
selection
1
F404H