67
F2-06 vector controlled slip gain
50%
~
200% [100%]
F2-07 SVC torque filter time constant
0.000s
~
0.100s [0.000s]
F2-09 torque upper limit source under speed control
mode
0
~
5 [0]
F2-10 torque upper limit digital setting under speed
control mode
0.0%
~
200.0% [150.0%]
In the speed control mode, the maximum output torque of the frequency inverter is controlled by the torque
upper limit source.
0: set by F2 - 10 digits.
1: AI1 analog setting.
2: AI2 analog setting.
3: AI3 analog setting.
4: XI pulse setting.
5: Communication settings.
Description:
F2 - 09 is used to select the setting source of the upper torque limit. When setting through analog quantity,
PULSE pulse and communication, 100 % of the corresponding setting corresponds to F2 - 10, while 100 % of F2 - 10
is the rated torque of the frequency inverter. For AI1, AI2, AI3, X5 settings, please refer to the introduction of F4 AI
curve.
When the selection is communication setting
The host computer writes -100.00%
~
100.00% of the data through the communication address 0x1000, of
which 100.00 % corresponds to F2 - 10.
F3 group V/F control parameters
This group of function codes is only valid for V/F control and invalid for vector control.
F3 - 00 V/F curve setting
0
~
11 [0]
0: straight line V/F.
Suitable for common constant torque load.
1: multipoint V/F.
Suitable for special loads such as dehydrators and centrifuges at this time, by setting F3 - 03 to F3 - 08
parameters, any desired VF relation curve can be obtained.
2: square V/F. Suitable for centrifugal loads such as fans and water pumps.
3 ~ 8: VF relation curve between straight line VF and square VF.
10: VF complete separation mode.