Defines the binding combination between three kinds of operation command channels and nine kinds of
frequency given channels to facilitate synchronous switching change.
The meaning of the given channel of the above frequency is the same as that of F0 - 03 selected by the main
frequency source X. please refers to F0 - 03 function code descriptions. Different run command channels can bind a
given channel with the same frequency.
When the command source has a bundled frequency source, other set frequency sources will no longer function
during the period when the command source is active.
F0 - 35 cooling fan control
0
~
1 [0]
0: fan running when running;
The frequency inverter operates the fan in the running state, the fan rotates when the radiator temperature is
higher than 40 degrees in the shutdown state, and the fan does not operate when the radiator temperature is lower
than 40 degrees in the shutdown state.
1: the fan has been running all the time;
The fan has been running since it was powered on.
F0 - 36 forward and reverse dead time
0.0s
~
3000.0s [0.0s]
Set the transition time at the output of 0 Hz during the forward and reverse transition of the frequency inverter, as
shown in figure 5 - 02:
Figure 5 - 02 schematic diagram of dead time for forward and reverse rotation
F0 - 37 Parameter 1 displayed at run time
0000
~
FFFF [H401F]
F0 - 38 Parameter 2 displayed at run time
0000
~
FFFF [H401F]
F0 - 39 Parameter 1 displayed at stop
0000
~
FFFF [H401F]
Please refer to the instructions in appendix 2.
Output frequency
Forward
Dead time
Reversal