77
F4-33 arbitrarily reaching current 1
0.0 % ~ 300.0 % ( rated current of motor ) [ 100.0 % ]
F4-34 the width of current 1 is arbitrarily reach 0.0 % ~ 300.0 % ( rated current of motor ) [ 0.0% ]
F4-35 arbitrarily reaching current 2
0.0 % ~ 300.0 % ( rated current of motor ) [ 100.0% ]
F4-36 the width of current 2 is arbitrarily reach 0.0 % ~ 300.0 % ( rated current of motor ) [ 0.0% ]
When the output current of the frequency inverter is set within the positive and negative detection width of any
arriving current, the multi-function DO (No. 28 and No. 29) of the frequency inverter outputs on signal.
HV610 provides two groups of random arrival currents and detection width parameters. The detection principle
is similar to F4 - 29 ~ F4 - 32.
F4 - 37 AI1 input voltage protection value lower
limit
0.00V
~
F4-38 [3.1V]
F4 - 38 upper limit of AI1 input voltage
protection value
F4-37
~
10.00V [6.8V]
When the analog input value of AI1 is greater than F4 - 38, or AI1 input value is less than F4 - 37, the
multi-function DO (31) of the frequency changer outputs an “AI1 input overrun" ON signal to indicate whether the
input voltage of AI1 is within the set range.
F4 - 39 module temperatures reached
0 ~ 100 [75°C]
When the frequency inverter radiator temperature reaches the temperature, the multi-function DO of the
frequency inverter outputs the “module temperature reaches" ON message
F4 - 40 zero current detection level
0.0 % ~ 300.0 % ( rated current of motor ) [ 5.0% ]
F4 - 41 zero current detection delay time
0.00s
~
600.00s [0.10s]
When the output current of the frequency inverter is less than or equal to the zero current detection level and the
duration exceeds the zero current detection delay time, the frequency inverter multifunction ( No. 34 ) DO outputs ON
signal.
F4 - 42 output current overrun value
0.0 % ( no detection );
0.1% ~ 300.0 % ( rated current of motor ) [ 200.0% ]
F4 - 43 output current overrun detection delay
time
0.00s
~
600.00s [0.00s]
When the output current of the frequency inverter is greater than or exceeds the limit detection point and the
duration exceeds the software over current point detection delay, the frequency inverter multifunction (No. 36) DO
outputs on signal.
F5 group input terminals
F5 - 00 XI terminal function selection
0
~
60 [1]
F5 - 01x2 terminal function selection
0
~
60 [2]
F5 - 02 x3 terminal function selection
0
~
60 [9]
F5 - 03x4 terminal function selection
0
~
60 [12]
F5 - 04x5 terminal function selection
0
~
60 [13]
F5 - 05x6 terminal function selection
0
~
60 [14]