PID value given
FA-01
25%
The set pressure is 2.5kg.
PID feedback source
FA-02
0
The pressure gauge is fed back to AI1 ( 0 ~ 10v input )
Name
Function code
Numerical
Description
PID feedback range
FA-04
1000
The measuring range of pressure gauge is 10kg
Proportional gain
FA-05
30
Integration time
FA-06
1
Selection of PID shutdown
operation
FA-28
1
Continue calculation when shutdown
Stress wake-up option
FA-29
1
Pressure wake-up is valid during sleep
Percentage of wake-up
pressure
FA-30
80%
It will be awakened when pipeline pressure is lower than 2.5 * 80 %
= 2kg
Wake - up delay time
FA-31
1s
Percentage of dormant
pressure
FA-32
100%
When the pipeline pressure is greater than the set pressure of
2.5kg, it goes to sleep after 60s.
Pressure sleep delay time
FA-33
60s
Type 2: The 4 ~ 20ma pressure transmitter
Modifies the following parameters based on the type 1 parameters, and the control board AI2 jumper is shorted to the
current input side
Name
Function code
Numerical
Description
AI2 minimum input
F5-29
2.00
2v correspond to 4mA
PID feedback source
FA-02
1
The feedback source is AI2 ( 4 ~ 20ma current signal )
4.1 The sleep wake-up function
Has two sleep modes. During the control process, one of them can be selected according to actual needs.
1) Sleep according to pressure, that is, after the pressure reaches the sleep pressure threshold, the frequency
inverter stops outputting after a delay time.
Stress wake-up option
FA-29
1
Pressure wake-up is valid during sleep
Percentage of wake-up
pressure
FA-30
80%
It will be awakened when pipeline pressure is lower than 2.5 * 80 %
= 2kg
Wake - up delay time
FA-31
1s
Percentage of dormant
pressure
FA-32
100%
When the pipeline pressure is greater than the set pressure of 2.5kg,
it goes to sleep after 60s.
2) Sleep according to the frequency, that is, the frequency is lower than the sleep frequency threshold. After the
delay time, the frequency inverter stops outputting.
Stress wake-up option
FA-29
0
Pressure wake-up is invalid during sleep ( according to wake-up
frequency )
Wakeup frequency
F8-14
40hz
When the set frequency is greater than 40hz, the frequency inverter wakes
up
Wake - up delay time
F8-15
1s
Sleep frequency
F8-16
25hz
When the set frequency is lower than 25hz, enter the sleep state after 60
seconds between F8 and 17 hours
3) No need to sleep
Stress wake-up option
FA-29
0
Pressure wake-up is invalid during sleep
Wakeup frequency
F8-14
0
Wake - up delay time
F8-15
0
Sleep frequency
F8-16
0