172
Inquiry method of state parameters
In the shutdown or running state, the > > shift key ON the operation panel switches the contents corresponding
to each byte of the function code F0 - 37 / 38 / 39 and can display multiple status parameters. There are 32 operating
state parameters in the operating state, and the function code F0 - 37 / 38 selects whether each corresponding
parameter is displayed according to the binary bit.
There are 13 shutdown state parameters under shutdown state, and the functional codes F0 - 39 select whether
each corresponding parameter is displayed according to the binary bit.
Correspondence between decimal system and hexadecimal system:
Decimal system
0123456789
10
11
12
13
14
15
Hexadecimal
0123456789
A
B
C
D
E
F
Examples:
Check the parameters in the running state through the panel: (running frequency, bus voltage, output voltage,
output current,Output power, PID setting).
1. According to the correspondence between each byte in the function code F0 - 37 and the above parameters,
the corresponding bit is set to 1.
2. Set this binary number to F0 - 37 after converting it to hexadecimal. Keyboard setting value: h 001f.
3. Use the > > key on the operation panel to switch the corresponding contents of each byte of the function code
F0 - 37 in turn, and you can check the values of relevant parameters. Set as shown in the figure below:
High position
Low position
F0-37
Binary
hexadecimal
Operating
parameter 1
Tens
Ones
kilobit
Hundreds
Running
Set frequency
Busbar voltage
Output voltage
Output current
Output power
Output torque
X output state
Do output state
AI1 voltage
AI2 voltage
AI3 voltage
Count value
Length value
Load speed
PID setting