F5 – 06 X7 terminals function selection
0 ~ 60 [8]
These parameters are used to set the functions of the digital multi-function input terminals and the functions that
can be selected are shown in the following table:
Setting
value
Functionalities
Description
0
Nonfunctional
The unused terminals can be set to “no function" to prevent
misoperation.
1
Forward run ( FWD )
The forward rotation and reverse rotation of the frequency
inverter are controlled through external terminals.
2
Reverse run (REV)
3
Three - wire operation control
Through this terminal, it is determined that the frequency
inverter operation mode is a three-wire control mode. Please
refer to the description of function code F5 - 11 (“terminal
command method”) for details.
4
Forward jog
(
FJOG
)
FJOG is inching forward rotation, RJOG is inching reverse
rotation. Refer to the function code for inching operation
frequency and inching acceleration / deceleration time
description of F6 - 13, F6 - 14, F6 - 15.
5
Reverse jog
(
RJOG
)
6
Terminal UP
The increment and decrement instructions of the frequency are
modified when the frequency is given by the external terminal.
When the frequency source is set to digital setting, the setting
frequency of the section can be adjusted up and down.
7
Terminal DOWN
8
Free parking
The frequency inverter blocks the output. At this time, the stop
process of the motor is not controlled by the frequency
changer.
9
Fault reset
(
RESET
)
The function of using terminals to reset faults. Same function
as reset key on keyboard. This function can be used to reset
the remote fault barrier.
10
Suspension of operation
The frequency inverter decelerates and stops, but all operating
parameters are memorized. Such as PLC parameters, swing
frequency parameters and PID parameters. After this terminal
signal disappears, the frequency inverter returns to the
operating state before parking.
11
External fault normally open input
When the signal is sent to the frequency inverter, the frequency
inverter reports the failure ETF.
12
Multi-segment command terminal 1
The speed of 16 segments can be realized through 16 States
of the four terminals. See attached table 1 for details.
13
Multi-segment command terminal 2
14
Multi-segment command terminal 3
15
Multi-segment command terminal 4
16
Acceleration and deceleration time
selection terminal 1
Through the four States of the two terminals, the choice
between the four acceleration and deceleration times can be
realized, see table 2 for details.
17
Acceleration and deceleration time
selection terminal 2
18
Frequency source switching
Used to switch and select different frequency sources.
According to the setting of the frequency source selection
function code (F0 - 32); this terminal is used to switch between
two frequency sources when switching between two frequency
sources is set as the frequency source.
19
UP/DOWN setting cleared ( terminal,
keyboard )
When the frequency is given as a digital frequency, this
terminal can clear the frequency value changed by the terminal
UP/DOWN or the keyboard UP/DOWN to restore the given
frequency to the value set in F0 - 09.