114
Figure 5 - 32 shutdown modes after single cycle
1: Maintain the final value at the end of a single run. As shown in figure 5 - 33, the frequency inverter
automatically maintains the operating frequency of the last section after completing one cycle.
Figure 5 - 33 PLC maintains final value after single cycle
2: Keep running in a cycle.
After the frequency inverter completes one cycle, it will automatically start the next cycle until there is a stop
command.
FC - 17 Simple PLC memory selection
00
~
11
【
00
】
Bit: power failure memory option.
0: no memory when power fails.
When power is lost, the PLC operation state will not be memorized. When power is turned on, the PLC will start
to run again from the first stage.
1: power failure memory.
When power is lost, the PLC operation status, including operation phase and frequency, and the time that has
already been run, will be memorized. Continue to run from the memory stage after power - up.
Ten digits: stop memory option.
0: stop the machine and do not remember.
Each start-up starts from the first stage.
1: stop memory.
PLC shutdown memory is to record the previous PLC operation phase and frequency during shutdown, and
continue to operate from the memory stage during the next operation.
Plc operation
Run command
Plc operation
Run command