73
Setting
value
Functionalities
Description
21
Reserve
Reserve
22
Reserve
Reserve
23
Zero speed operation in 2 ( also input
during shutdown)
When the output frequency of the frequency inverter is 0, the
on signal is output. This signal is also in shutdown state.
24
Cumulative power-on time arrives
When the frequency inverter's accumulated power-on time (U0
- 71) exceeds the time set by F8 - 00, the frequency inverter
outputs an on signal.
25
Frequency level detection FD T2
output
Please refer to the descriptions of function codes F4 - 26 and
F4 - 27.
26
Frequency 1 reaches output
Please refer to the descriptions of function codes F4 - 29 and
F4 - 30.
27
Frequency 2 reaches output
Please refer to the descriptions of function codes F4 - 31 and
F4 - 32.
28
Current 1 reaches output
Please refer to the descriptions of function codes F4 - 33 and
F4 - 34.
29
Current 2 reaches output
Please refer to the descriptions of function codes F4 - 35 and
F4 - 36.
30
Timed arrival output
When the timing function selection (F8 - 04) is valid, the on
signal will be output after the current running time of the
frequency inverter reaches the set timing time.
31
Ai1 input overrun
When the value of analog input AI1 is greater than F4 - 37 (AI1
input protection upper limit) or less than F4 - 38 (AI1 input
protection lower limit), the signal is input.
32
Off loading
When the frequency inverter is in the off-load state, an ON
signal is output.
33
In reverse operation
When the frequency inverter is in reverse operation, an ON
signal is output.
34
Zero current state
Please refer to the descriptions of function codes F4 - 33 and
F4 - 34
35
Module temperature reached
When the frequency inverter module radiator temperature ( U0
- 69 ) reaches the set module temperature reaching value ( F4
- 39 ), an ON signal is output
36
Software current overrun
Please refer to the descriptions of function codes F4 - 42 and
F4 - 43.
37
Lower limit frequency reached
( shutdown also output )
When the operating frequency reaches the lower limit
frequency, an ON signal is output. This signal is also ON during
shutdown.
38
Alarm output
When the frequency inverter fails and the processing mode of
the failure is continuous operation, the frequency inverter gives
an alarm output.
39
The running time has arrived
When the starting operation time of the frequency inverter
exceeds the time set by F8 - 07, the on signal is output.
40
Fault output
Under voltage does not output.
41
AI1 is lower than lower limit output
When the value of AI1 is lower than F4 - 37, output
42
AI1 above upper limit output
When AI1 value is higher than F4 - 38, output
43
AI2 output below lower limit
When AI2 value is lower than F4 - 37, output
44
AI2 above upper limit output
When AI2 value is higher than F4 - 38, output
F4-06 FMP output function selection ( pulse output terminal )
0
~
16 [0]
F4-07 AO1 output function selection
0
~
16 [0]
F4-08 AO2 output function selection
0
~
16 [1]