31
Function
code
Name
Setting range
Factory
value
Communica
tion address
F4-26
Frequency detection
value ( FDT2 )
0.00Hz ~ maximum frequency
50.00Hz
F41AH
F4-27
Frequency detection lag
value ( FDT2 )
0.0 % ~ 100.0 % ( FDT2 level )
5.0%
F41BH
F4-28
Frequency reaches
detection width
0.0 % ~ 100.0 % ( maximum frequency )
0.0%
F41CH
F4-29
Random arrival
frequency check value 1 0.00Hz ~ maximum frequency
50.00Hz
F41DH
F4-30
Random arrival
frequency detects width
1
0.0 % ~ 100.0 % ( maximum frequency )
0.0%
F41EH
F4-31
Random arrival
frequency check value 2 0.00Hz ~ maximum frequency
50.00Hz
F41FH
F4-32
Random arrival
frequency detects width
2
0.0 % ~ 100.0 % ( maximum frequency)
0.0%
F420H
F4-33
Arbitrarily reaching
current 1
0.0 % ~ 300.0 % ( rated current of motor )
100.0%
F421H
F4-34
The width of current 1 is
arbitrarily reach
0.0 % ~ 300.0 % ( rated current of motor )
0.0%
F422H
F4-35
Arbitrarily reaching
current 2
0.0 % ~ 300.0 % ( rated current of motor )
100.0%
F423H
F4-36
The width of current 2 is
arbitrarily reach
0.0 % ~ 300.0 % ( rated current of motor )
0.0%
F424H
F4-37
AI1 input voltage
protection value lower
limit
0.00V
~
F4-38
3.10V
F425H
F4-38
AI1 upper limit of input
voltage protection value F4-37
~
10.00V °C
6.80V
F426H
F4-39
Module temperature
reached
0°C
~
100°C
75°C
F427H
F4-40
Zero current detection
level
0.0% ~ 300.0%
100.0 % corresponding motor rated current
5.0%
F428H
F4-41
Zero current detection
delay time
0.01s
~
600.00s
0.10s
F429H
F4-42
Output current overrun
value
0.0 % ( no detection )
0.1 % ~ 300.0 % ( rated current of motor )
200.0%
F42AH
F4-43
Output current overrun
detection delay time
0.00s
~
600.00s
0.00s
F42BH
F5 group input terminals
F5-00
X1 input terminal
function selection
0: no function
1: forward run FWD or run command
2: reverse operation REV or reverse operation
direction ( note: when set to 1 and 2, it should be
used in conjunction with F5 - 11. for details,
please refer to the description of function code
parameters )
3: three-wire operation control
4: Forward jog
(
FJOG
5: reverse jog
(
RJOG
)
6: terminal UP
1
F500H
F5-01
X2 input terminal
function selection
2
F501H