![HNC Electric HV480 Series User Manual Download Page 46](http://html.mh-extra.com/html/hnc-electric/hv480-series/hv480-series_user-manual_2142004046.webp)
42
Function
code
Name
Setting range
Factory
value
Communica
tion address
FB-03
Rated current of motor
0.01A ~ 655.35A ( frequency inverter power ≤
55kW ) 0.1A ~ 6553.5A ( frequency inverter
work rate > 55kW )
Model
determin
ation
FB03H
FB-04
Rated frequency of
motor
0.01Hz ~ maximum frequency
Model
determin
ation
FB04H
FB-05
Rated speed of motor
1rpm
~
65535rpm
Model
determin
ation
FB05H
FB-06
Stator resistance of
asynchronous motor
0.001
~
65.535
( frequency inverter power ≤ 55kW) 0.0001 ~
6.5535 ( frequency inverter power > 55kW )
Model
determin
ation
FB06H
FB-07
Rotor resistance of
asynchronous motor
0.001
~
65.535
( frequency inverter power ≤ 55kW) 0.0001 ~
6.5535 ( frequency inverter power > 55kW )
Model
determin
ation
FB07H
FB-08
Induction motor leakage
reactance
0.01 mH ~ 655.35 mH( frequency inverter power
≤ 55kW) 0.001 mH ~ 65.535 mH ( frequency
inverter power > 55kW )
Model
determin
ation
FB08H
FB-09
Mutual inductance
reactance of
asynchronous motor
0.1 mH ~ 6553.5 mH( frequency inverter power
≤ 55kW) 0.01 mH ~ 655.35 mH ( frequency
inverter power > 55kW )
Model
determin
ation
FB09H
FB-10
Asynchronous motor
no-load current
0.01A
~
FB-
03(frequency inverter power ≤ 55kW)0.1A
~
FB
- 03 ( frequency inverter power > 55kW )
Model
determin
ation
FB0AH
FB-29
Tuning selection
0: no operation
1: asynchronous machine static tuning
2. asynchronous machine fully tuned
0
FB1DH
FB-38
Velocity loop proportional
gain KP1
1
~
100
30
FB26H
FB-39
Speed loop integral gain
KI1
0.01s
~
10.0s
0.50s
FB27H
FB-40
Switching frequency 1
0.00
~
FB-43
5.00Hz
FB28H
FB-41
Velocity loop proportional
gain KP2
1
~
100
20
FB29H
FB-42
Speed loop integral gain
KI2
0.01s
~
10.00s
1.00s
FB2AH
FB-43
Switching frequency 2
FB-40
~
maximum frequency
10.00Hz
FB2BH
FB-44
Vector controlled slip
gain
50%
~
200%
100%
FB2CH
FB-45
SVC torque filter
constant
00
~
31
0.000s
FB2DH