117
FD Group communication parameters
Please refer to appendix a: description of communication parameters of FD group.
FE Group user-defined function code
This group function code is a user-defined parameter group.
The user can select the required parameters from all HV610 function codes and summarize them to the Fe
group as user-customized parameters.
Number to facilitate viewing and changing operations The Fe group provides up to 30 user-defined parameters,
and the displayed value of the Fe group parameter is f 0.00, which indicates the user function code is empty.
When entering the user-defined parameter mode, the display function codes are defined by FE-00
~
FE-31. The
order is the same as that of the FE group function codes. If F0 - 00, it will be skipped.
FF Group control optimization parameters
FF - 04
cbc current limiting enable
0
~
1
【
0
】
0: not enabled.
1: enabling wave-by-wave current limiting.
By enabling the wave-by-wave current limiting function, the over-current fault of the frequency inverter can be
minimized and the frequency inverter can be guaranteed to run uninterruptedly.
FF – 06
Uder voltage point setting
60%
~
140%
【
100.0%
】
Voltage value of frequency inverter under voltage fault LV
FF – 09
over voltage point setting
200.0V
~
2200.0V
【
820.0V
】
Note: the factory value is also the upper limit value of the internal over voltage protection of the frequency
inverter. This parameter setting will only take effect if the FF - 09 setting value is less than the factory value. If it is
higher than the factory value, the factory value shall prevail.
E0 Group fault record
E0-00
First failure type
0
~
99
【
0
】
E0-01
Second failure type
0
~
99
【
0
】
E0-02
Third ( most recent ) fault type
0
~
99
【
0
】
E0-03
Frequency at third failure
0.00
~
500.00
【
0.00HZ
】