Figure 5 - 07 V/F separation shutdown process diagram
F4 group output terminals
F4 - 00 FM terminal output mode selection
0
~
1 [0]
The FM terminal is a programmable multiplex terminal, which can be used as a high-speed pulse output terminal
(FMP) or as a switch output terminal (FMR) with open collector.
0: high-speed pulse output terminal.
When outputting FMP as pulse, the highest frequency of the output pulse is 100 kHz. See F4 - 06 for FMP
related functions instruction.
1: Open collector output terminal.
When switching output is used, the output function is set by F4 - 01 function code.
F4-01 FMR Open collector output terminal
0
~
42 [0]
F4-02 relay output function selection
(
T/A-T/B-T/C
)
0
~
42 [2]
F4-04 DO1 open collector output terminal
0
~
42 [0]
The function of the multi-function output terminal is explained as follows:
Setting
value
Functionalities
Description
0
No output
The output terminal has no function
1
The frequency inverter is in operation
Indicates that the frequency inverter is running and has an
output frequency (which can be zero). At this time, the on
signal is output.
Output voltage
Time
Time
Output frequency
F3 - 17 = 0 V/F independent deceleration mode
F3 - 17 = 1 first step-down and then step-down mode
T2 t1 is that actual time require to reduce the voltage to
zero
T2 is that actual time require to reduce the frequency to
zero
T2 t1 is that actual time require to reduce the voltage to zero
T2 is that actual time require to reduce the frequency to zero