S1 series standard inverter
-122-
Function
code
Name
Detailed parameter description
Default
value
Modify
HDI/HDIA
P05.49
HDI/HDIA
frequency input
filter time
0.000s
–10.000s
0.030s
○
P05.50
Lower limit
frequency of
HDIB
0.000 KHz
– P05.47
0.000
KHz
○
P05.51
Corresponding
setting of lower
limit frequency of
HDIB
-100.0%
–100.0%
0.0%
○
P05.52
Upper limit
frequency of
HDIB
P05.45
–50.000KHz
50.000
KHz
○
P05.53
Corresponding
setting of upper
limit frequency of
HDIB
-100.0%
–100.0%
100.0%
○
P05.54
HDIB frequency
input filter time
0.000s
–10.000s
0.030s
○
P05.55
AI1 input signal
type
0: Voltage type
1: Current type
Note:
You can set the AI1 input signal type
through the corresponding function code (up to
2.2kW the AI1 is set by protentiometer).
0
◎
P06 group Output terminals
P06.00
HDO output type
0: Open collector high-speed pulse output: Max.
frequency of the pulse is 50.00kHz. For details
about the related functions, see P06.27
–P06.31.
1: Open collector output: For details about the
related functions, see P06.02.
Note: up to 2.2kW there is no HDO terminal.
0
◎
P06.01 Y output selection 0: Invalid
1: In running
2: In forward running
3: In reverse running
4: In jogging
5: Inverter fault
0
○
P06.02
HDO output
selection
0
○
P06.03
Relay RO1 output
selection
1
○
P06.04 Relay RO2 output
5
○