S1 series standard inverter
-150-
Function
code
Name
Detailed parameter description
Default
value
Modify
P14.05
Transmission
error processing
0: Alarm and coast to stop
1: Do not alarm and continue running
2: Do not alarm and stop as per the stop mode
(under communication control mode only)
3: Do not alarm and stop as per the stop mode
(under all control modes)
0
○
P14.06
Communication
processing action
0x00
–0x11
Ones:
0: Write operation has response
1: Write operation has no response
Tens:
0: Communication password protection is invalid
1: Communication password protection is valid
0x00
○
P17 group State-check function
P17.00
Set frequency
Display current set frequency of the inverter.
Range: 0.00Hz
–P00.03
50.00Hz
●
P17.01 Output frequency
Display current output frequency of the inverter.
Range: 0.00Hz
–P00.03
0.00Hz
●
P17.02
Ramps reference
frequency
Display current ramps reference frequency of the
inverter.
Range: 0.00Hz
–P00.03
0.00Hz
●
P17.03
Output voltage
Display current output voltage of the inverter.
Range: 0
–1200V
0V
●
P17.04
Output current
Display the valid value of current output current of
the inverter.
Range: 0.0
–5000.0A
0.0A
●
P17.05
Motor speed
Display current motor speed.
Range: 0
–65535RPM
0 RPM
●
P17.06
Torque current
Display current torque current of the inverter.
Range: -3000.0
–3000.0A
0.0A
●
P17.07
Exciting current
Display current exciting current of the inverter.
Range: -3000.0
–3000.0A
0.0A
●
P17.08
Motor power
Display current motor power; 100% relative to
rated motor power, positive value is motoring
state, negative value is generating state.
Range: -300.0
–300.0% (relative to rated motor
power)
0.0%
●
P17.09
Motor output
Display current output torque of the inverter;
0.0%
●