S1 series standard inverter
-60-
Function
code
Name
Detailed parameter description
Default
value
frequency
P01.03
DC brake current before start 0.0
–100.0%
0.0%
P01.04
DC brake time before start
0.00
–50.00s
0.00s
P01.05
Acceleration/deceleration
mode
0: Straight line
1: S curve
Note: If mode 1 is selected, it is required
to set P01.07, P01.27 and P01.08
accordingly
0
P01.08
Stop mode
0: Decelerate to stop
1: Coast to stop
0
P01.09
Starting frequency of DC
brake after stop
0.00Hz
–P00.03 (Max. output frequency)
0.00Hz
P01.10
Waiting time of DC brake
after stop
0.00
–50.00s
0.00s
P01.11
DC brake current of stop
0.0
–100.0%
0.0%
P01.12
DC brake time of stop
0.00
–50.00s
0.00s
P01.13
Deadzone time of
forward/reverse rotation
0.0
–3600.0s
0.0s
P01.14
Forward/reverse rotation
switch-over mode
0: switch over after zero frequency
1: switch over after starting frequency
2: switch over after passing stop speed
and delay
0
P01.15
Stop speed
0.00
–100.00Hz
0.50 Hz
P01.16
Stop speed detection mode
0: Set value of speed (the only detection
mode valid in V/F mode)
1: Detection value of speed
1
P01.18
Power-on terminal running
protection selection
0: Terminal running command is invalid
at power up
1: Terminal running command is valid at
power up
0
P01.19
Action selection when the
running frequency is below
lower limit (lower limit should
be larger than 0)
0: Run at the lower limit frequency
1: Stop
2: Sleep
0
P01.20
Wake-up-from-sleep delay
0.0
–3600.0s (valid when P01.19
is 2)
0.0s
P01.21
Restart after power down
0: Restart is disabled
1: Restart is enabled
0