S1 series standard inverter
-41-
Function
code
Name
Detailed parameter description
Default
value
operations are done, this function code
will be restored to 0 automatically.
Restoration to default value will clear the
user password, this function should be
used with caution.
P02.01
Rated power of
asynchronous motor 1
0.1
–3000.0kW
Depend
on model
P02.02
Rated frequency of
asynchronous motor 1
0.01Hz
–P00.03 (Max. output frequency)
50.00Hz
P02.03
Rated speed of
asynchronous motor 1
1
–36000rpm
Depend
on model
P02.04
Rated voltage of
asynchronous motor 1
0
–1200V
Depend
on model
P02.05
Rated current of
asynchronous motor 1
0.8
–6000.0A
Depend
on model
P05.01
–
P05.06
Function of multi-function
digital input terminal
(S1
–S4, HDIA, HDIB)
36: Command switches to keypad
37: Command switches to terminal
38: Command switches to communication
/
P07.01
Parameter copy
0: No operation
1: Upload the local function parameter to the
keypad
2: Download the keypad function parameter
to local address (including the motor
parameters)
3: Download the keypad function parameter
to local address (excluding the motor
parameter of P02 and P12 group)
4: Download the keypad function parameters
to local address (only for the motor
parameter of P02 and P12 group)
Note
: After finish 1
– 4, the parameter will
restore to 0 and the uploading and
downloading does not include P29.
0
P07.02
QUICK/JOG key function
Range: 0x00
–0x27
Ones: QUICK/JOG key function selection
0: No function
1: Jogging
2: Reserved
3: Switching between forward/reverse
rotation
4: Clear UP/DOWN setting
5: Coast to stop
0x01