S1 series standard inverter
-105-
Function
code
Name
Detailed parameter description
Default
value
Modify
P03 group Vector control of motor
P03.00
Speed loop
proportional gain 1
Parameters of P03.00
–P03.05 fit for vector
control mode only. Below P03.02, speed loop PI
parameter is P03.00 and P03.01; above P03.06,
speed loop PI parameter is P03.03 and P03.04; in
between, PI parameter is obtained by linear
variation between two groups of parameters, as
shown below.
Output frequency f
PI parameter
P03.02
P03.05
P03.03
,
P03.04
P03.00
,
P03.01
The speed loop dynamic response characteristics
of vector control can be adjusted by setting the
proportional coefficient and integral time of speed
regulator. Increase proportional gain or decrease
integral time can accelerate dynamic response of
speed loop, however, if the proportional gain is
too large or integral time is too small, system
oscillation
and
overshoot
may
occur;
if
proportional gain is too small, stable oscillation or
speed offset may occur.
Speed loop PI parameter is closely related to the
system inertial, users should make adjustment
based on default PI parameter according to
different load characteristics to fulfill different
needs.
Setting range of P03.00:0.0
–200.0;
Setting range of P03.01: 0.000
–10.000s
Setting range of P03.02: 0.00Hz
–P03.05
Setting range of P03.03: 0.0
–200.0
Setting range of P03.04: 0.000
–10.000s
Setting range of P03.05: P03.02
–P00.03 (Max.
output frequency)
20.0
○
P03.01
Speed loop
integral time 1
0.200s
○
P03.02
Switch low point
frequency
5.00Hz
○
P03.03
Speed loop
proportional gain
2
20.0
○
P03.04
Speed loop
integral time 2
0.200s
○
P03.05
Switch over high
point frequency
10.00Hz
○
P03.06
Speed loop
0
–8 (corresponds to 0–2^8/10ms)
0
○