S1 series standard inverter
-128-
Function
code
Name
Detailed parameter description
Default
value
Modify
running time
P07.15
High bit of
inverter power
consumption
Display the power consumption of the inverter.
power consumption=P07.15×1000+P07.16
Setting range of P07.15: 0
–65535 kWh (×1000)
Setting range of P07.16: 0.0
–999.9 kWh
/
●
P07.16
Low bit of inverter
power
consumption
/
●
P07.17 Dual ratings
0: ND rating
1: LD raing
/
/
P07.18
Rated power of
inverter
0.4
–3000.0kW
/
●
P07.19
Rated voltage of
inverter
50
–1200V
/
●
P07.20
Rated current of
inverter
0.1
–6000.0A
/
●
P07.21 Factory barcode 1 0x0000
–0xFFFF
/
●
P07.22 Factory barcode 2 0x0000
–0xFFFF
/
●
P07.23 Factory barcode 3 0x0000
–0xFFFF
/
●
P07.24 Factory barcode 4 0x0000
–0xFFFF
/
●
P07.25 Factory barcode 5
0x0000
–0xFFFF
/
●
P07.26 Factory barcode 6
0x0000
–0xFFFF
/
●
P07.27
Type of present
fault
0: No fault
1: Inverter unit U phase protection (OUt1)
2: Inverter unit V phase protection (OUt2)
3: Inverter unit W phase protection (OUt3)
4: Overcurrent during acceleration (OC1)
5: Overcurrent during deceleration (OC2)
6: Overcurrent during constant speed (OC3)
7: Overvoltage during acceleration (OV1)
8: Overvoltage during deceleration (OV2)
9: Overvoltage during constant speed (OV3)
10: Bus undervoltage fault (UV)
11: Motor overload (OL1)
12: Inverter overload (OL2)
13: Phase loss on input side (SPI)
14: Phase loss on output side (SPO)
15: Rectifier module overheat (OH1)
16: Inverter module overheat (OH2)
/
●
P07.28
Type of the last
fault
/
●
P07.29
Type of the last
but one fault
/
●
P07.30
Type of the last
but two fault
/
●
P07.31
Type of the last
but three fault
/
●
P07.32
Type of the last
but four fault
/
●